How to display only active alarms in Vista or Diagrams for export in PME 7 & 8?
Issue
User wants a list of all current active alarms that can be exported to excel
Product
StruxureWare Power Monitoring (SPM) 7.0.x
Power Monitoring Expert (PME) 7.2.x, 8.x
Environment
Vista and Web Diagrams
Resolution
1) Open Vista and select a current diagram or create a new diagram
2) With the diagram toolbox open, drag and drop a new datalog viewer object
3) Setup the datalog viewer and edit the query and copy and paste the following query.
SELECT [SourceName]
,[SourceType]
,dbo.DateAsUnix(TimestampUTC) AS timestamp
,[Priority]
,[Cause]
,[CauseValue]
,[Effect]
,[EffectValue]
,[AckTimeUTC]
,[AckUserName]
,[AckRemark]
FROM [ION_Data].[dbo].[vAlarmLog]
where endID is null and (not type = 0) and priority > 64
order by timestamputc desc
4) Save the diagram and open datalog viewer in Vista or web diagram
5) Copy the contents of the table to excel
User wants a list of all current active alarms that can be exported to excel
Product
StruxureWare Power Monitoring (SPM) 7.0.x
Power Monitoring Expert (PME) 7.2.x, 8.x
Environment
Vista and Web Diagrams
Resolution
1) Open Vista and select a current diagram or create a new diagram
2) With the diagram toolbox open, drag and drop a new datalog viewer object
3) Setup the datalog viewer and edit the query and copy and paste the following query.
SELECT [SourceName]
,[SourceType]
,dbo.DateAsUnix(TimestampUTC) AS timestamp
,[Priority]
,[Cause]
,[CauseValue]
,[Effect]
,[EffectValue]
,[AckTimeUTC]
,[AckUserName]
,[AckRemark]
FROM [ION_Data].[dbo].[vAlarmLog]
where endID is null and (not type = 0) and priority > 64
order by timestamputc desc
4) Save the diagram and open datalog viewer in Vista or web diagram
5) Copy the contents of the table to excel
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.