What causes Concept Modbus connection error 'OL9-1501 Timed out waiting for response from controller'.

Issue:

What causes Concept Modbus connection error 'OL9-1501 Timed out waiting for response from controller'.

Product Line:

Concept

Resolution:

Troubleshooting:

  • If configured for MB RTU mode, switch to ASCII mode. Put switch in ASCII position and connect to MB1 with ASCII 7, 1, even.
  • If using USB converter, turn off wireless card , if present.
  • Disable AB drivers
  • Confirm pinout of Modbus cable.

MB parameters correct?  9600, 8, 1, even

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance: