How can we help you today?
What causes Concept Modbus connection error 'OL9-1501 Timed out waiting for response from controller'.
Issue:
What causes Concept Modbus connection error 'OL9-1501 Timed out waiting for response from controller'.
Product Line:
Concept
Resolution:
Troubleshooting:
- If configured for MB RTU mode, switch to ASCII mode. Put switch in ASCII position and connect to MB1 with ASCII 7, 1, even.
- If using USB converter, turn off wireless card , if present.
- Disable AB drivers
- Confirm pinout of Modbus cable.
MB parameters correct? 9600, 8, 1, even
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.