How can we help you today?

How do I troubleshoot the Altivar Process Drive when it will not connect or communicate while over a Modbus Serial Network?

Resolution:

If your drive is not connecting or communicating over a Modbus serial network, the issue is typically related to wiring, network configuration, communication settings, or control setup. Use the steps below as a basic troubleshooting guide.

Drive Will Not Connect

1. Verify Installation

  • Ensure a Modbus serial cable (not Ethernet) is connected to the correct port.
  • Confirm proper pin wiring based on the required pinout.
  • Minimize electrical interference:
    • Use separate conduits for control and power wiring
    • Add terminating resistors if the drive is the last device on the network

2. Check Network Configuration

  • Make sure there are no duplicate Modbus addresses on the network.
  • Verify all network devices are properly configured and compatible.

3. Confirm Drive Communication Settings
In the drive settings, verify:

  • Modbus Address
  • Baud Rate
  • Other serial parameters (parity, stop bits if applicable)

After making changes, always power cycle the drive.

4. Check Status Indicators

  • Review the drive’s LED indicators:
    • The Modbus (Eth NS) LED shows communication status
    • Use LED behavior to confirm if the network is active or faulted. Eth NS (Embeded Modbus) - Indicates the Modbus serial link connection status​

​Frontal LEDs​

Drive Connects But Will Not Run

    1. Verify Communication

    2. Check Control Configuration

    • Confirm the drive is set to Network Control
    • Path: [Complete Settings] → [Command and Reference]
    • Verify:
      • Command source
      • Frequency reference source

    3. Review Communication Mapping

    • Navigate to: [Display] → [Communication Map]
      Ensure the correct registers are assigned for command and reference values

    4. Validate Command Channels

    • Check:
      • Command register
      • Reference frequency channel
      • Reference frequency value
    Most Modbus communication issues result from incorrect wiring, mismatched communication settings, or improper control configuration. Systematically checking each area—hardware, network, and programming—will help restore proper communication.

    If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

    Frequently Asked Questions - Schneider Electric (se.com)

    If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

    If you are not located in North America, please contact your local Customer Care Center for assistance:

    Support | Schneider Electric Global (se.com)

    Schneider Electric UK

    Discuss this topic with experts

    Visit our community and get advice from experts and peers on this topic and more

    Explore more

    Need help?

    Product Selector

    Quickly and easily find the right products and accessories for your applications.

    Get a Quote

    Start your sales inquiry online and an expert will connect with you.

    Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

    Help Centre

    Find support resources for all your needs, in one place.