Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Error A320 on a LXM32 drive
Issue:
What is error A320 on a LXM32 drive?

Product Line:
Lexium 32

Resolution:
A320 is a following error. The parameter is _SigLatched Bit 8.
The difference between the commanded position and actual position is greater than the allowable setting.
Reason could be a high external load or an acceleration that is too high.
Solution is to reduce external load or acceleration or use a differently rated drive. This could also call for tuning the motor.
Error response can be adjusted via parameter ErrorResp_p_dif

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings