Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Does 140NOE77110 work with 140CPU67160
Question:
Does 140NOE77110 work with 140CPU67160 as we found it not able to configure(grey out) in UP11?

Answer:
140NOE77110 works with 140CPU67160 in hardware perspective.
UP11 masks this selection since 140NOE77110 is obsolete & 140NOE77111 is the alternative module.
If customer uses UP3.0, he could configure the 140NOE77110 with 140CPU67160.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings