ATS01N222RT Can you do a soft stop?
Issue:
How do I get the ATS01 to soft stop?
Product Line:
ATS01 Altistart 01 Altivar
Environment:
ATS01.....RT
Cause:
Need soft stopping.
Resolve:
If you have a jumper between LI2 and LI+ terminals, you will have soft starting with line power and a coast to stop when line power is removed.
If you have a start-stop signal that closes LI2 to LI+ to start, it will soft start according to the start dial. When you open this contact it will soft stop (decelerate) according to the stop dial setting.