What are the maximum number of fault current operations Ringmaster and GenieEvo will clear?

The number of faults that a circuit breaker can clear will depend on the level of fault current being interrupted.

Ringmaster: -
  • 16kA - the circuit breaker is designed to clear a maximum number of 11 times at 16kA fault current
  • 21kA - the circuit breaker is designed to clear a maximum number 10 times at 21kA fault current

GenieEvo is designed to clear a maximum of 100 faults at 25kA.

The fault current rating of the unit is detailed on the unit rating plate.