ATV320U15N4C: Is it possible to know the average and/or max power consumption when the motor is not active?
Issue:
Average and/or max power consumption when the motor is not active on an ATV320U15N4C.
Product Line:
ATV320
Environment:
ATV320U15N4C
Cause:
8 - Installation / Setup
Resolution:
In Ready state, motor not running :
1) Without any option board, no load on +24V :
Total losses : 6W
2) Worst : With Option board and full load on +24V (100mA)
Total losses : 15W
Average and/or max power consumption when the motor is not active on an ATV320U15N4C.
Product Line:
ATV320
Environment:
ATV320U15N4C
Cause:
8 - Installation / Setup
Resolution:
In Ready state, motor not running :
1) Without any option board, no load on +24V :
Total losses : 6W
2) Worst : With Option board and full load on +24V (100mA)
Total losses : 15W
Released for: Schneider Electric UK