How can we help you today?
ATV630 series drives, How do I bring the total input impedance up to 5%? The drive catalog shows 3% internal impedance already, do we add a 2% reactor?
Issue:
The ATV630 series drives have 3% impedance standard, is there a way to bring that up to 5%?
Product Line:
ATV600 series process drives.
Environment:
All models, All serial numbers
Cause:
Information unavailable in current literature.
Resolution:
In order to bring the equivalent input impedance of the ATV600 series drives to 5%, add a 3% line reactor ahead of the drive, not 2%. The input impedance is not linear so a 2% reactor added to the 3% internal equivalent impedance will not yield 5% input impedance.
The ATV630 series drives have 3% impedance standard, is there a way to bring that up to 5%?
Product Line:
ATV600 series process drives.
Environment:
All models, All serial numbers
Cause:
Information unavailable in current literature.
Resolution:
In order to bring the equivalent input impedance of the ATV600 series drives to 5%, add a 3% line reactor ahead of the drive, not 2%. The input impedance is not linear so a 2% reactor added to the 3% internal equivalent impedance will not yield 5% input impedance.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.