Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
What is the difference between DIO_HEALTH and RIO_HEALTH found in M580 Device DDT?

Issue:

M580 DDT has the below elements, customer wants to know what the device differences
Customer believes that the DROP_HEALTH  DDT corresponds to the BM•CRA312•0 drops  (up to a maximum of 32 BM•CRA312•0 modules).

But what is the difference between the following. What are these monitoring?
1. RIO_HEALTH  ARRAY [257...384] of BOOL  RIO devices: One array element corresponds to one RIO device (up to a maximum of 128 RIO devices).
RIO stands for Remote IO

2. DIO_HEALTH  ARRAY [513...640] of BOOL  DIO devices: One array element corresponds to one DIO device (up to a maximum of 128 DIO devices).
DIO stands for Distributed IO

Product Line:
M580

Environment:
EcoStruxure Control Expert
Unity Pro

Resolution:

In a 'probable' future, we may have some Ethernet devices (not CRA drops) scanned by RIO scanner (ATV is a good example)
So we will have then the 3 different devices :

  • DROP = CRA
  • DIO (devices) = devices scanned by DIO scanner of the CPU / NOC for best effort communications
  • RIO (devices) = devices scanned by RIO scanner of the CPU for deterministic communications

DIOxRIO

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings