Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
What would cause the ATV630 drive to have a surging motor when the drive is running in auto mode?
Issue:
The ATV630 drive is surging the motor when the drive is running in auto mode.

Product Line:
ATV630

Environment:
All

Cause:
Analog input was getting interference noise and analog input was oscillation up and down.

Resolution:
Check to see if you're experiencing noise on his line causing motor/drive fluctuations. If so, activate the applicable analog input filter (AI1F or AI2F). Set to 5 seconds.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings