How configure VMWare in mode NAT and SoMachine for M251 communication via ETH 2 port

Use the following method with the VMWare configured in NAT mode:

1. Configure SoMachine the communication via "active path":
Project Settings
2.In the Communication Settings window , add a gateway and use the IP address of the physique PC.
Add gateway
3.Select the new gateway and  Scan it
Scan Network
4. Now you can connect to the M251