How can we help you today?

How to establish an Ethernet/IP communication when T->O transfert format is 32 Bit Run/Idle in SoMachine/Machine Expert?

1. Import the slave .eds file in SoMachine/Machine Expert:

-

2. Add the device in the Industrial Ethernet Manager for M241/251 controllers or Ethernet/IP Scanner for M262 controllers:

-

3. Add a Generic connection:

-

4. In the application, skip the first two %IW in the Ethernet IP I/O Mapping:

-
=> The first two %IW will show the Status of the slave. You will find the input values from the third %IW.

Schneider Electric UK

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.