Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Can you use one large line reactor on multiple drives vs one line reactor for one drive?
Issue:
Is it possible to use one large line reactor on multiple drives vs one line reactor for one drive?

Product Line:
Altivar Drives

Environment:
All

Cause:
Would like to use only one line reactor and feed multiple drives.

Resolution:
No, it is best to have individual line reactors. If a single line reactor is used, it will have lower inductance and may not be enough if a single drive is running.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings