Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
What should the F601 current limit parameter be set to in the ATV212 drives?
Issue:
ATV212 parameter F601 configuration

Product Line:
ATV212, S-Flex 212

Environment:
All

Cause:
What should the F601 current limit parameter be set to in the ATV212 drives?

Resolution:
The F601 Current limit parameter should be set to 110% of the Drives current rating.
Note: If you use a small size motor on a larger drive, you will need to adjust this setting to the motor FLA times 1.1.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings