Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
How do I perform ATV630 and ATV930 Basic Programming?

Article available in these languages: Spanish, Korean

Issue:
Basic Programming on an Altivar Process Drive.

Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)

Environment:
All serial numbers for Altivar Process Drive

Cause:
Initial setup / maintenance

Resolution:
Using the keypad or our SoMove programming software, be sure to go through the Simply Start Menu to perform your basic settings:

From the Main Menu select [Simply start]:

[Motor Standard] bFr -            50Hz IEC or 60Hz NEMA- motor nameplate

[Nominal motor power] nPr -   Motor HP - motor nameplate

[Nom Motor Voltage] UnS -      Motor voltage - motor nameplate

[Nom Motor Current] nCr -       Motor FLA - motor nameplate

[Nominal Motor Freq] FrS -      60Hz in the US - motor nameplate

[Nominal Motor Speed] nSP - Actual motor max speed, not Synchronous speed unless it is a synchronous motor - motor nameplate

[2/3-Wire Control] tCC -           Factory default is '2-Wire Control'

[Max Frequency] tFr -              Max frequency of the motor, usually 60Hz - motor nameplate

[Autotuning] tUn -                    No Action, Apply Autotuning, Erase Autotuning

[Autotuning Status] tUS -         Displays 'Not Done' unless Autotuning is performed

[Motor Th Current] ItH -            Motor thermal current - motor nameplate - used to set the motor overload protection level

[Acceleration] ACC -                 Acceleration time in seconds

[Deceleration] dEC -                 Deceleration time in seconds

[Low Speed] LSP -                    Minimum speed, drive will never run lower than this speed when given a run command

[High Speed] HSP -                  Maximum speed, drive will never run higher than this speed when given a run command


In many instances these parameters will be enough to sufficiently program a drive. If any further programming is required (such as PID, command/reference switching, hoisting, etc), please refer to the applicable Programming Manual for your drive.

Refer to the applicable manual for further details:
ATV600 series Programming Manual
ATV900 series Programming Manual

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings