PM810 Energy Summary Usage and Energy Per Shift Usage Modbus Register read a value of 0

Title
PM810 Energy Summary Usage and Energy Per Shift Usage Modbus Registers Return 0

Language
English

Issue
Energy Summary Usage and Energy Per Shift Usage Modbus registers return a value of 0 when read from a PM810 meter.

Product Line
PM800
PM810
PM820
PM850
PM870

Note: PM810 is a legacy, reduced‑feature device. Energy Summary Usage and Energy Per Shift Usage are not supported on this model.

Environment
Modbus communications
Energy data acquisition

Cause
The PM810 does not support Energy Summary Usage or Energy Per Shift Usage calculations.

Although the Modbus register list shows the Float registers (11864 to 11958) as supported, these values are derived from MOD10 registers (16202 to 16346) that are not implemented on the PM810. As a result, the derived Float registers do not return valid data.

Resolution
Energy Summary Usage and Energy Per Shift Usage are not supported on the PM810.

When these Modbus registers are read on a PM810 meter, they will return a value of 0. This is expected behavior and cannot be corrected through configuration or firmware changes.

If Energy Summary Usage or Energy Per Shift Usage values are required, use one of the following meters that support this capability:

  • PM820
  • PM850
  • PM870

Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.