How can we help you today?
Sepam 80 - pulse mode for Logic Outputs. What is the default pulse width for this mode?
For the Sepam 80 (and Sepam 60) relays, the pulse width for certain Logic Outputs can be set in SFT2841.
By default, the pulse width for the O1 tripping output is 200 milliseconds. For certain other outputs on the MES120 input / output modules such as O101, this default width is 300ms.
Please see the attached file for details. The results in the attached file were tested using firmware version V8.xx and SFT2841 software version V15.1.
AEDL3
By default, the pulse width for the O1 tripping output is 200 milliseconds. For certain other outputs on the MES120 input / output modules such as O101, this default width is 300ms.
Please see the attached file for details. The results in the attached file were tested using firmware version V8.xx and SFT2841 software version V15.1.
AEDL3
Released for: Schneider Electric UK
Attachment(s)
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.