VIDEO: Testing Citect Credentials Fail for Application Services Host

Issue
A users credentials fail to authenticate in Application Configuration Utility > Application Services Host:
image
Citect connection unavailable.
Note: Citect runtime must be running to perform this test

Note: Citect Runtime is already running.


Product Line
PowerSCADA Expert 8.1, 8.2, 9.0 (PSE 8.x, 9.x)

Environment
Application Configuration Utility

Cause
A successful connection by the Schneider Electric ApplicationServiceHost service requires a user already defined in the PowerSCADA project, server IP address and a parameter in the INI file.  However, testing citect credentials will not work if it's running as a service. In this resolution, the INI parameter is missing.


Resolution
1.  In Citect INI file, set [ctAPI] Remote = 1.

image


2.  Shutdown and restart the Runtime (project).

3.  Now the test will succeed:
image

**Embed video here**

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center