How can we help you today?
What is the lost of power per pole for K30 to K150 cam switches
K30: 1.3W
K50: 1.3W
K63: 1.7W
K115 : 5.8W
K150: 3.8W
K50: 1.3W
K63: 1.7W
K115 : 5.8W
K150: 3.8W
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.