Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Video: How do we export Alarm Group data from one project to another project in Vijeo Designer?
Issue:
How do we export Alarm Group data from one project to another project in Vijeo Designer?

Product Line:
Vijeo Designer (all versions)

Resolution:
To export alarm group data from one project to another project in Vijeo Designer, follow this procedure:

1) Ensure both the new and old application have an alarm group with same name
2) In the old application, goto variables in the navigator window and right-click. Choose "Export Variables"
3) Save the variable csv file somewhere on your PC
4) On the new application, goto variables in the navigator window and right-click. Choose "Import Variables"
5) Find the csv file on your PC and press the open button.

This will bring your alarm data into the new project.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings