Video: How do we export Alarm Group data from one project to another project in Vijeo Designer?

Issue:
How do we export Alarm Group data from one project to another project in Vijeo Designer?

Product Line:
Vijeo Designer (all versions)

Resolution:
To export alarm group data from one project to another project in Vijeo Designer, follow this procedure:

1) Ensure both the new and old application have an alarm group with same name
2) In the old application, goto variables in the navigator window and right-click. Choose "Export Variables"
3) Save the variable csv file somewhere on your PC
4) On the new application, goto variables in the navigator window and right-click. Choose "Import Variables"
5) Find the csv file on your PC and press the open button.

This will bring your alarm data into the new project.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.