Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
How to disable Ring/Network coupling operation and set coupling port free on connexium managed switches ?
Connexium switch applies default port / operation settings based on Dip Switch positions set and it over rides any custom configuration done during next power cycle. So to free up port for use  assigned to coupling and to turn OFF operation of Ring/Coupling Network , a custom configuration has to be applied to switch.Makes sure to put dip switch both RM & Standby in ON position and do settings for Hiper Ring redundancy etc and Operation to OFF for ring networking coupling and  coupling port can be left at default. Doing this will free up coupling port to connect any devices.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings