How can we help you today?

Have the Pedestal and Deadband been reversed on the Process Drives compared to the ATV61/71 drives?

Issue:
The Pedestal and Deadband appear to have been reversed on the Process Drives compared to the ATV61/71 drives.

Product Line:
ATV630, ATV930

Environment:
Pedestal and deadband

Cause:
n/a

Resolution:
Response from France:
We are aware about that and we are waiting for the solution.
Appears to be a problem on the keypad and SoMove.
Parameter BSP can have a setting of Standard, Pedestal, Deadband or Deadband 0 % :
When you see the Keypad: BSP can be standard , Deadband, pedestal or pedestal at 0%:
The term is inverted on keypad : Deadband should be Pedestal and pededstal /pedestal at 0% should Deadband/Deadband at 0%.
Same problem with SoMove:
The solution to set Pedestal like on ATV71, is to set Deadband on ATV6XX/ATV9xx.
We have asked for a solution on future softwares on the Keypad and SoMove.

Schneider Electric UK

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.