Cannot log in to FlexNet Publisher in PME 8.2

Issue
User cannot log in to the FlexNet Publisher web interface in Power Monitoring Expert (PME) 8.2 and receives a “Password is incorrect” message, even when using known credentials.

Product Line
Power Monitoring Expert 8.2

Note: Legacy article. This behavior applies to the FlexNet Publisher licensing implementation used in PME 8.2.

Environment
FlexNet Publisher (lmadmin)
Power Monitoring Expert licensing

Cause
In PME 8.2, FlexNet Publisher user credentials may not function as expected due to changes in license server configuration or credential initialization. The FlexNet Publisher web interface and administrator account still exist, but access can fail if the stored credentials are invalid or corrupted.

Resolution
Warning: This procedure involves editing configuration files. Always back up files before making changes.

Use the following steps to reset the FlexNet Publisher administrator password:

  1. Navigate to:
    C:\ProgramData\Schneider Electric\Floating License Manager\FLEXnet Publisher License Server Manager\conf
  2. Open the server.xml file in a text editor.
  3. Locate the administrator entry and update the password value, for example:
    id="admin" lastName="Administrator" password="(ENC-01)AxlKxBaCLbp4iPFsjJ6eOFtE+qoJWH8ThHIKN9DgdEgILS9j" passwordExpired="false"
  4. Save the file.
  5. Restart the lmadminschneider service.
  6. Open a browser and navigate to:
    http://<SERVERNAME>:8090
  7. Click Administration and log in using:
    Username: admin
    Password: admin

Recommendation

If you are using an older version of PME, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo.support@se.com

Support Information

Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.