How can we help you today?

How to use revenue lock switch in PM8000 meter ?

You can lock and unlock your meter using the revenue lock switch located on the
meter base.

1. Turn off all power supplying this device and the equipment in which it is installed
before working on the device or equipment.
2. Always use a properly rated voltage sensing device to confirm that all power is
off.
3. Open the revenue lock switch cover.
4. Locate the revenue lock switch.
5. Toggle revenue lock switch on or off.
6. Close the revenue lock switch cover and make sure it is firmly in place.
7. Seal the revenue lock switch cover if required.

Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.