Can I use 2 potentiometers in parallel to control the speed of the drive from 2 different locations?
Issue:
Is it possible to control speed of drive using 2 potentiometers in different locations?
Product Line:
All Altivar drive products.
Environment:
All models, All serial numbers
Cause:
Customer needs to be able to control the speed of the drive from 2 different locations at the same time.
Resolution:
No, this is not possible by using parallel potentiometers. The drive will only follow a single speed reference at any given time.
The drive can be switched between two different potentiometers via a logic input but it can not follow two different potentiometers at once.
Some drives allow 2 separate analog input signals to be summed or added together to set the speed reference.
Is it possible to control speed of drive using 2 potentiometers in different locations?
Product Line:
All Altivar drive products.
Environment:
All models, All serial numbers
Cause:
Customer needs to be able to control the speed of the drive from 2 different locations at the same time.
Resolution:
No, this is not possible by using parallel potentiometers. The drive will only follow a single speed reference at any given time.
The drive can be switched between two different potentiometers via a logic input but it can not follow two different potentiometers at once.
Some drives allow 2 separate analog input signals to be summed or added together to set the speed reference.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.