Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
What form is a powerpact 4 panel board?
Form Type
Powerpact 4 panel boards are Form 3b type 2 as standard.
Form 4 type 2 & 6 can be achieved by use of individual disconnectable neutral links adjacent to breakers or by the use of 4 pole breakers. Outgoing terminals must be shrouded with long terminal shields. The main neutral bar either side of the incomer need to be removed and discarded together with the connecting copper bar. The incoming breaker should be a 4 pole breaker

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings