How can I connect to my ATV drive with SoMove through an M251MESE (with IP forwarding) ?
Network topology is as following :
- Subnetwork 192.168.10.x : PC with SoMove connected to M251MESE port 1
- Subnetwork 192.168.100.x : M251MESE port 2 connected to ATV600 (or any other ATV with ethernet port)
PC :
192.168.10.1
255.255.255.0
M251 Port1 :
192.168.10.51
255.255.255.0
"Enable IP forwarding" checkbox enabled
M251 Port2 :
192.168.100.51
255.255.255.0
ATV600 :
192.168.100.60
255.255.255.0
Gateway : 192.168.100.51
On PC side the following command has to be entered in command prompt :
route add 192.168.100.0 MASK 255.255.255.0 192.168.10.51
- Subnetwork 192.168.10.x : PC with SoMove connected to M251MESE port 1
- Subnetwork 192.168.100.x : M251MESE port 2 connected to ATV600 (or any other ATV with ethernet port)
PC :
192.168.10.1
255.255.255.0
M251 Port1 :
192.168.10.51
255.255.255.0
"Enable IP forwarding" checkbox enabled
M251 Port2 :
192.168.100.51
255.255.255.0
ATV600 :
192.168.100.60
255.255.255.0
Gateway : 192.168.100.51
On PC side the following command has to be entered in command prompt :
route add 192.168.100.0 MASK 255.255.255.0 192.168.10.51
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.