Can the C120H and iC120H MCBs be fitted into the Isobar and Acti 9 distribution boards?

The C120H and iC120H breakers do not fit in any distribution board.

The C120H and iC120H circuit breakers do not fit because they are 27mm wide per pole, where as the C60H range are 18mm wide per pole.
It is possible to feed/cable off the pan assembly of the Isobar or Acti 9 distribution board using the SEA9TB1001 terminal block (1 per phase) and cable into a din extension enclosure with the C120H or iC120H breakers in but only to a maximum of 100amps.