How can we help you today?
How many S908 (140CRA31908) networks are permitted in an M580 ERIO application?
Issue:
How many S908 (140CRA31908) networks are permitted in an M580 ERIO application?
Product Line:
140CRA31908
Resolution:
You can have one S908 network in an M580 application. (140CRA31908).
If you're using M580 HSBY you are allowed a second 140CRA31908 in order to achieve redundancy on the RIO network.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.