How can we help you today?
Cannot communicate to Siemens S7-1200 PLC configured with TIA portal
Issue:
Magelis HMI is unable to communicate to a Siemens S7-1200 PLC
Product Line:
Vijeo Designer, Magelis HMI with Ethernet
Resolution:
If your Magelis HMI cannot communicate with your Siemens S7-1200 PLC configured with TIA portal, try enabling the setting below in TIA:
(Protection->Connection->Connection mechanisms)
Permit access with PUT/GET communication from remote partner (PLC, HMI,OPC...)
Magelis HMI is unable to communicate to a Siemens S7-1200 PLC
Product Line:
Vijeo Designer, Magelis HMI with Ethernet
Resolution:
If your Magelis HMI cannot communicate with your Siemens S7-1200 PLC configured with TIA portal, try enabling the setting below in TIA:
(Protection->Connection->Connection mechanisms)
Permit access with PUT/GET communication from remote partner (PLC, HMI,OPC...)
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.