How do I setup the Altivar Process Drive to communicate over CanOpen?
Issue:
Altivar Process Drive setup to communicate over CanOpen
Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)
Environment:
All serial numbers for Altivar Process Drive
Cause:
N/A
Resolution:
This FAQ will go over some basic settings to check. For a more detailed list of procedures on setting up the drive for CanOpen please reference the manuals attached.
EDS Files
- Programming with the Drive
Altivar Process Drive setup to communicate over CanOpen
Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)
Environment:
All serial numbers for Altivar Process Drive
Cause:
N/A
Resolution:
This FAQ will go over some basic settings to check. For a more detailed list of procedures on setting up the drive for CanOpen please reference the manuals attached.
EDS Files
- Download and import CanOpen EDS files
- ATV600
- CANopen v1.1 - VW3A36x8: https://www.se.com/ww/en/download/document/ATV600_CANopen_EDS_V1_1/
- CANopen v1.2 - VW3A36x8: https://www.se.com/ww/en/download/document/ATV600_CANopen_EDS_V1_2/
- CANopen v1.3 - VW3A36x8: https://www.se.com/ww/en/download/document/ATV600_CANopen_EDS_V1_3/
- CANopen v1.4 - VW3A36x8: https://www.se.com/ww/en/download/document/ATV600_CANopen_EDS_V1_4/
- CANopen v1.5 - VW3A36x8: https://www.se.com/ww/en/download/document/ATV600_CANopen_EDS_V1_5/
- CANopen v1.6 - VW3A36x8: https://www.se.com/ww/en/download/document/ATV600_CANopen_V1_6/
- ATV900
- CANopen v1.1 - VW3A36x8: https://www.se.com/ww/en/download/document/ATV900_CANopen_V1_1/
- CANopen v1.2 - VW3A36x8: https://www.se.com/ww/en/download/document/ATV900_CANopen_V1_2
- ATV600
- Programming with the Drive
- Program Communication Settings:
- [Communication] COM, [CANopen] CnO
- [CANopen Address] AdCo
- This is a read/write parameter. The parameter number is 6051 via Modbus access
- [CANopen Baudrate] bdCO
- This is a read/write parameter. The parameter number is 6053 via Modbus access.
- [CANopen Error] ErCO
- This is a read-only Parameter. The parameter number is 6056 via Modbus access..
- [CANopen Address] AdCo
- [Communication] COM, [CANopen] CnO
- Program Command Settings:
- [Complete settings] [Command and Reference]
- For command speed from Network, program:
- [Ref Freq 1 Config] Fr1 - Set to [CANopen] CAn
- [Ref 1B switching] rCb - Set to [Ref Freq Channel 1] Fr1
- [Control Mode] CHCF - Set to [Not separ.] SIM
- Video: Setting an Auto/Manual or Reference Switching on the Altivar Process Drives
- For command speed from Network, program:
- [Complete settings] [Command and Reference]
- Powercycle the drive
- [Parameters List] [Fieldbus] [Slot A - CanOpen]
- Configure
- CanOpen Address, Baud Rate & Error
- Configure
- Sending a command to the drive
- Configuration of the Drive for Operation in I/O Profile
- [Complete Settings] [Command and Reference] [Control Mode] - Set to IO
- Command Word - CanOpen Register 2037/2
Speed Reference Word - CanOpen Registers 2037/3 (Hz) or 2038/3 (rpm) - 16 bit word (Bit 0, 1, 2..... 15)
- Start/Stop for FWD command must turn on bit 0
- Write a 1 to start
- Write a 0 to stop
- Bit 1 to 15 are assignable like logic inputs
- Example: To assign a fault reset to bit 7 - [Fault reset] - Set to Cd07 (Reference Programming manual for more details)
- Using CIA402 (DriveCom Profile)
- Works with other assemblies
- [Complete Settings] [Command and Reference] [Control Mode] to [Not separ.] or [Separate]
- Command Word - CanOpen Register 2037/2
Speed Reference Word - CanOpen Registers 2037/3 (Hz) or 2038/3 (rpm) - No 16 bit word
- Start/Stop
- Sequence of values must be written to the drive
- 6, 7 and 15
- Toggle between 7 and 15 to start and stop or "RDY" to "RUN"
Released for: Schneider Electric UK
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.