PlantStruxure PES [V4.1]: How to configure Peer2Peer communications (controller to controller) in PES

Goals and Symptoms

The purpose of this document is to summarize the Peer2Peer communications features available in PES 4.1 and to provide typical examples that can be found in real projects.

Facts and Changes

This document has been created for PES version 4.1.

Causes and Fixes

Peer2Peer communications means data exchange between controllers, which is a common requirement in DCS systems. Peer2Peer communication is implemented in PES system using Modbus TCP implicit messaging (IO Scanner) as the communication channel.
It is possible to define a Peer2Peer communication channel between a controller communication card with Modbus TCP/IP having IO scanner capability and a controller that acts as a Modbus TCP/IP server. On top of this communication channel, using PES it’s possible to add a certain amount of “network variables”.

A network variable is a Unity variable (elementary or derived) defined in a certain control project (having the role of the “owner”) whose value has to be transferred to another control project (having the role of the “consumer”).

This document describe difference aspect of Peer2Peer communication in both owner controller and consumer controller.

Schneider Electric UK

Attachment(s)
Peer2Peer communications in PES 4.1.pdf [2.35 MB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center