How do you set up the analog input on the ATV630 and ATV930 for a current 0 to 20mA input?
Issue:
Analog input setup on the ATV630 and ATV930 for a current 0 to 20mA signal
Product Line:
ATV630 ATV930
Environment:
All
Cause:
Wants to set up AI1 for 0 to 20mA for speed control
Resolution:
Setting up AI1 as a 0 to 20mA input.
Using the HMI display
Go to the Main Menu
Go to the Complete settings
Go to the Inputs and outputs
Choose the 3rd function key black tab AI/AO
Go to the AI1 configuration
Go to AI1 type
Choose Current
Set AI1 min value to 0mA
Set AI1 Max value to 20mA.
Programming manual link
https://www.se.com/us/en/download/document/EAV64318/
Analog input setup on the ATV630 and ATV930 for a current 0 to 20mA signal
Product Line:
ATV630 ATV930
Environment:
All
Cause:
Wants to set up AI1 for 0 to 20mA for speed control
Resolution:
Setting up AI1 as a 0 to 20mA input.
Using the HMI display
Go to the Main Menu
Go to the Complete settings
Go to the Inputs and outputs
Choose the 3rd function key black tab AI/AO
Go to the AI1 configuration
Go to AI1 type
Choose Current
Set AI1 min value to 0mA
Set AI1 Max value to 20mA.
Programming manual link
https://www.se.com/us/en/download/document/EAV64318/
Released for: Schneider Electric UK
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.