How can we help you today?

Connecting an EGX150 to a serial RS485

Issue
The Serial port for the EGX150 uses an RJ45 connector, which is different from the standard RS-485 connector.

Product Line
Link150, EGX150

Environment
EGX150 serial connections

Cause
The EGX150 does not use the standard RS-485 connector.

Resolution

Table 1: Connector RJ 45 Pinout

Pin Number

Color

Signal name

Description

1

Orange/White striped

Rx-

Receive Data -

2

Orange

Rx+

Receive Data +

3

NC

No Connection

4

Blue

Tx+

Transmit Data +

5

Blue/white striped

Tx-

Transmit Data -

6

-

NC

No Connection

7

-

NC

No connection

8

-

GND

Ground












Connect, using a straight through RJ45 cable to the RS-485 port on your EGX150.
Cut the other end (that is to be connected to your slave device) to expose the wires.

A1. 2-Wire RS-485 connection


Use the Blue wire as the positive (+) and the Blue/White striped wire as the negative (-)

A1. 2-Wire RS-485 connection

A2. RS-485 2-Wire with Link150 Cable Adapter Connection Diagram

A2. RS-485 2-Wire with Link150 Cable Adapter Connection Diagram


B1. 4-Wire RS-485 connection

B1. 4-Wire RS-485 connection

Table 2: RJ45 Master/Slave Pinout

RJ45 Pin Number

Master

Slave

1

Rx-

Tx-

2

Rx+

Tx+

4

Tx+

Rx+

5

Tx-

Rx-









B2. RS-485 4-Wire with Link150 Cable Adapter Connection Diagram


B2. RS-485 4-Wire with Link150 Cable Adapter Connection Diagram


Kindly refer to the EGX150 User Guide for details on how to wire the RS-485 port.

Schneider Electric UK

Explore more

Range:

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Range:

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.