Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
What is a start check warning (code 46) on a Tesys T LTMR product?
Issue:
Customer is receiving error 46 Start Check on their Tesys T product.

Product Line:
TeSys T - LTMR

Environment:
US Product

Cause:
Product Specification

Resolution:
Start command check (Error 46) signifies that current is not detected after a delay of 1 second after a start command.  The unit must see a current equal to or more than 10% of FLC minimum.  If the unit is being tested without a motor load, ensure that a current of more than 10% FLC minimum is being passed through the internal CT windows of the device.

Schneider Electric UK

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings