What would cause the ATV320 drive to power up with a blank display?
Issue:
The ATV320 drive powers up with a blank display.
Product Line:
ATV320
Environment:
All
Cause:
Power board is inoperative or rectifier circuit is inoperative.
Resolution:
Troubleshooting
Check Line voltage on L1, L2, L3 to make sure it is balanced and correct.
Check the DC bus voltage across PA(+) and PC(-). It should be (line voltage) x 1.414. [eg 480V x 1.414 = 678Vdc]. If not, the rectifier is inoperative.
Check the +24Vdc-COM voltage. If sagging, remove the 24V wiring to see if the external circuitry is shorting out the supply.
Drive will need to be replaced if it is found to be inoperative.
The ATV320 drive powers up with a blank display.
Product Line:
ATV320
Environment:
All
Cause:
Power board is inoperative or rectifier circuit is inoperative.
Resolution:
Troubleshooting
Check Line voltage on L1, L2, L3 to make sure it is balanced and correct.
Check the DC bus voltage across PA(+) and PC(-). It should be (line voltage) x 1.414. [eg 480V x 1.414 = 678Vdc]. If not, the rectifier is inoperative.
Check the +24Vdc-COM voltage. If sagging, remove the 24V wiring to see if the external circuitry is shorting out the supply.
Drive will need to be replaced if it is found to be inoperative.
Released for: Schneider Electric UK
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.