How can we help you today?
PME : Changing Database server name in PME product uninstaller
Issue
While attempting to run the PME product uninstaller, the user is unable to change the 'Database Server' name as the field is greyed out within the window.
Product Line
Power Monitoring Expert 8.x
Power Monitoring Expert 9.0
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Environment
PME Uninstaller
Cause
In a standalone/distributed system environment, the database instance server name may have been changed inadvertently without following the correct procedure for server name changes.
Resolution
*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).
1. Navigate to the following directory: C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\Uninst_PowerMonitoringExpert
2. Open the 'InstallInfo.xml' document in Notepad for editing.
3. Change the following parameters and point them to the current database server name.
- globalMachineName
- globalMachineFQDN
- globalEEMDBName
- globalEEMDbServer
Example:
globalMachineName="WTCALVSE010WYMD" globalMachineFQDN="WTCALVSE010WYMD.nam.gad.schneider-electric.com" globalEEMDBName="WTCALVSE010WYMD" globalEEMDbServer="WTCALVSE010WYMD"
Released for: Schneider Electric UK
Explore more
Product:
Range:
Explore more
Product:
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.