Can I connect 2 sets of current sensors on the Sepam 80?
Yes, two sets of current sensors can be connected to a Sepam series 80.
Both traditional current sensors (current transformers CT In/5A or In/1A) and LPCT sensors can be connected.
Only Sepam series 80 using transformer earth leakage protection (Sepam T87, M88 and G88) do not allow the use of LPCT sensors.
For further information, please see online Sepam user manual.