How can we help you today?

With an RM6, can I use DIN fuses instead of FUSARC fuses?

No, only FUSARC CF or SIBA fuses are compatible with RM6 cubicles. FUSARC fuses are specified in DIN 43625.

Schneider Electric UK

Explore more

Range:

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Range:

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.