PME/PSE 8.x: Starting the Floating License Manager in 'Expert' mode

Issue
Starting the floating license manager in expert mode.

Product Line
Power Monitoring Expert 8.x

Power Monitoring Expert 9.x

PowerSCADA Expert 8.x

Environment
Floating License Manager

Cause
Modify and/or delete corrupted PME/PSE licenses.

Resolution
1. Create a shortcut of the 'FloatingLicenseManager.exe' file found at the following default directory:
C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\Floating License Manager

2. Right-click on the 'Floating License Manager' shortcut file and select 'Properties'.
Add 'expert' after the following entry in the Target parameter: "C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\Floating License Manager\FloatingLicenseManager.exe"
E.g. "C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\Floating License Manager\FloatingLicenseManager.exe" expert

Shortcut target path

3. Click 'OK' in the properties window to apply and save the changes.

Note: PME 2021 and later use the License Configuration Tool

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center