How can we help you today?
Does BMENOC0301 support hold the last value
Question:
Customer has setup his M580 NOC0301 comm with another PLC's NOC using Ethernet IP.
Comm is working all good, however, on his Local Slave side, he wants to be able to change Input Fallback Mode from Set to Zero to Hold the last value but it appears it is grayed out.
Does BMENOC0301 support hold the last value?
Answer:
No, In its current implementation, Ethernet/IP scanner does not support "hold the last value" as input fallback strategy for EIP Devices.
Customer has setup his M580 NOC0301 comm with another PLC's NOC using Ethernet IP.
Comm is working all good, however, on his Local Slave side, he wants to be able to change Input Fallback Mode from Set to Zero to Hold the last value but it appears it is grayed out.
Does BMENOC0301 support hold the last value?
Answer:
No, In its current implementation, Ethernet/IP scanner does not support "hold the last value" as input fallback strategy for EIP Devices.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.