What are the main differences between feeder and motor mode with Easergy P3?
Issue:
Need to understand the main differences between feeder mode and motor mode in Easergy/Powerlogic P3.
Product Line:
- Easergy/ Powerlogic P3
- Applies to Easergy/Powerlogic P3 relays that support feeder and motor application modes
Environment:
- Easergy/Powerlogic P3 relay configuration
- Application mode selection
- Protection function configuration
Cause:
Feeder mode and motor mode use different scaling references and enable different protection functions based on the selected application.
Resolution:
- In feeder mode, current scaling is based on the CT nominal.
- In motor mode, current scaling is based on the motor nominal current (Imot).
- Some protection functions appear or disappear depending on the selected mode.
- In feeder mode, feeder-related functions such as auto recloser are available.
- In motor mode, motor-related functions such as motor start-up supervision and other motor protection functions are available.
- Common protection functions, such as overcurrent protection, may be available in both modes, but their settings and scaling are interpreted according to the selected application mode.
- If the expected function is not visible, verify that the relay is configured for the correct application mode.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.