How can we help you today?

Why can’t I find some of the expected protection functions in the “Protection” menu?

Easergy P3 has a dynamic behaviour and will hide functions which are not possible to use e.g. due to missing measurement. Please check your voltage measurement mode initially. Notice also that some of functions might allow to use calculated value but some not. E.g. intermittent earth fault function must have a measured Uo value so a 3LN voltage measurement mode will hide this function.

Schneider Electric UK

Explore more

Range:

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Range:

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.