How can we help you today?
How to Configure a Third Stage of Neutral Voltage Displacement Protection (59N) on a Powerlogic P3 protection relay
Issue
The device provides only two dedicated stages of neutral voltage displacement (59N), but the customer requires three stages.
Product
Powerlogic P3 protection relay
Environment
Protection function configuration – Neutral Voltage Displacement (59N)
Cause
The standard protection package includes only two predefined 59N stages. Additional stages must be configured manually using programmable protection stages.
Resolution
To add a third 59N stage:
- Activate one of the eight programmable stages available in the device.
- Set the input coupling to Uo.
- Configure the threshold and settings in the same manner as one of the dedicated 59N stages.
- Save and apply the configuration.
This provides functionality equivalent to an additional 59N stage.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.