Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
If I connect to the Easergy P3 device, how can I create a SCL file for all the signals?

Initially ensure that all menus are uploaded, after connecting to the device with eSetup Easergy Pro select upload icon and “Read all settings”.

Next select all signals used to “In use” under Communication/data maps. Then select tool icon and “Export ICD/SCL file…”.

Before generation you need to define if RCB names should include indexes (typically selected) and if the file should be in Ed.1 or Ed.2 format.

If Edition 2 extensions ae selected the file will have Ed.2 format, otherwise Ed.1 format. When saving the file there is the possibility to save the format as .icd, .iid or .cid.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings