How can we help you today?

On Ativars ATV61, ATV71, can I use PTC connected to LI6 and external 24V for logic inputs at the same time?

Yes it is possible. Wiring in attachment
Do not forget to set SW2 switch = PTC
To enable PTC monitoring, in Drive menu - Fault management - LI6 as PTC = (anything different from "no")

Schneider Electric UK

Attachment(s)
Pict_scheme.jpg [75.27 KB]
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center