Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
What is the meaning of the Max switch-on time parameter valid for an external braking resistor connected to the Servo drive Lexium LXM32
Resext_on, the max permissible switch-on time for external braking resistor is max continuous period for current delivered to external braking resistor. After this time at the latest, there must be a "pause" inserted. During the pause, no current is delivered to the braking resistor. The purpose is to balance resistor temperature and to avoid a high rise of temperature followed by long fall (cooling during pause).
The parameter should not be greater than 10% of the resistor time constant.
On the other hand, the parameter should not be very small as it can limit the current delivery and braking dynamics for high inertia loads.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings