Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
What level of current flow triggers an SCF3 fault on an ATV61 or ATV71 series drive?

Issue:
ATV61 or ATV71 current flow that triggers an SCF3

Product Line:
ATV61 / ATV71 series

Environment:
All models, All serial numbers

Cause:
Information not available in current literature.

Resolution:
SCF3 faults:
The purpose of this function is to detect a short circuit to the ground at the start-up or while running.

Detection time:
Quick hardware detection (a few μs) . Output current sum > 25% of the current rating of the drive.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings